Product Line:

Tesys GV Manual Starter and Protectors
 
Resolution:
Toggle operated thermal magnetic motor protector for use on motors with high peak currents at start-up or for switching the primaries of 3-phase transformers. Listed below are the thermal and magnetic setting ranges:

Values listed below are in Amps.
Controller Thermal Range Magnetic Trip (+/-20%)
GV2RT03 0.25 - 0.40 8
GV2RT04 0.40 - 0.83 13
GV2RT05 0.63 - 1.00 22
GV2RT06 1.00 - 1.60 33
GV2RT07 1.60 - 2.50 51
GV2RT08 2.50 - 4.00 78
GV2RT10 4.00 - 6.30 138
GV2RT14 6.00 - 10.0 200
GV2RT16 9.00 - 14.0 280
GV2RT20 13.0 - 18.0 400
GV2RT21 17.0 - 23.0 400


 