Technical FAQs

Ask a Question

What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

Issue:
Identifying power terminal lug data for the D2 style contactors

Product Line:
Tesys D line contactors

Environment:
Products sold and used in the United States

Cause:
Power terminal lug data required

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.


CTA-ID : 2016948
Was this helpful?
What can we do to improve the information ?