Technical FAQs

Ask a Question

What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

Issue:
Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

Product Line:
NEMA combination starters

Environment:
Products sold and used in the United States

Cause:
Power terminal lug data required

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
stranded cable w/cable end: One or Two #18-10 AWG per terminal.
solid cable: One or Two #18-8 AWG per terminal.


CTA-ID : 2016945
Was this helpful?
What can we do to improve the information ?