Does the XCKJ10541limit switch have a neutral position, or is it right or left motion only?

The ZCKE05 head can be programmed to be at rest in the center position, left, or right. Remove the head and change the programming with the black knob underneath. This is not a neutral position, where one set of contacts changes when the lever moves left, and the other set of contacts changes when the lever moves right of center. To obtain a neutral position switch, ZCKJ404 is the body and head combination that would support this.