Can the new Powerpact breakers be tested with the universal tester UTS3?

Issue:
Can the new Powerpact breakers be tested with the universal tester UTS3?

Product Line:
Powerpact Circuit Breakers

Environment:
Products used and supported in the US

Cause:
Breaker testing

Resolution:
No. Secondary injection testing of these breakers would require the Full Function test kit S33595 or the Handheld test kit S33594 for Powerpact P and R-frame breakers, or UTA tester STRV00910 for Powerpact H, J, and L-frame breakers.