What is the lug wire range for HCP235912N?

The actual wire range of the main lugs is (4) #3/0 - 750MCM per phase and neutral. The acceptable wire range per NEC Table 373-6 is (4) #3/0 - 500MCM based on the available wire bending space in the standard enclosure. If incoming cables are larger than 500MCM, an extended end gutter may be required.

NOTE: Extended end gutters are only available on NEMA 1 enclosures.

Revised 3/11/04