What is the lug wire range for HCP235912N and will it accept up to 750KCMIL?

Issue:
Will a HCP235912N accept 3 conductors larger than 500KCMIL?

Product Line:
Panel

Environment:
I-line HCP 1200A Panel

Cause:
Needed larger incoming lugs

Resolution:
The actual wire range of the main lugs is (4) #3/0 - 750MCM per phase and neutral. The acceptable wire range per NEC Table 373-6 is (4) #3/0 - 500MCM based on the available wire bending space in the standard enclosure. If incoming cables are larger than 500MCM, an extended end gutter may be required.

NOTE: Extended end gutters are only available on NEMA 1 enclosures. Please refer to the Suplemental Digest or your local distributor for a part number.






 