If I change a Size 2 solid state overload mounted on an 8536 NEMA Size 2 starter to a Size 1 solid state overload, will it mount directly to the contactor?

The standard size 1 solid state overload relay (9065SS110, 9065SS120, or 9065SF120) will not fit directly to a size 2 starter/contactor. Use the 9065SR112 (Class 10), 9065SR122 (Class 20), or 9065ST122 (Class 10/20). 2016276.