Technical FAQs

Ask a Question

What is the contact voltage rating on an 8501CO relay?

Issue:
What is the contact voltage rating on an 8501CO relay?

Product Line:
Power Relays

Environment:
All products

Cause:
Product Specifications

Resolution:
This relay is rated at 600V, 30A.

Contact Rating:

SPST - NO- DM (CO6) DPDT _ N.O. (CO7)
SPST - N.C.- DB (CO8)
30A @ 300V 50/60Hz 30A @ 300v 50/60Hz
12A @ 480V 50/60Hz 5 A @ 480V 50/60Hz
10A @ 600V 50/60Hz 5A @ 600V 50/60Hz
2 HP 120-600V 50/60Hz 1 1/2HP ea. pole 12-600 50/60Hz
30 A@ 28V DC Resistive 2 HP SW 2 poles 200-600V 50/60Hz
10A Tung @ 120V 50/60Hz 30A @ 28V DC Resistive
10A tung @ 120V 50/60Hz


CTA-ID : 2015714
Was this helpful?
What can we do to improve the information ?