Which weathershield kit do we select for a stainless steel (grade #316; painted) ventilated Transformer (enclosures 17D through 31D) to obtain a Nema 3R rating?

Weathershields for Ventilated Transformers

Product Line:
LV Transformers

Applies to Low Voltage Transformers by SquareD/Schneider Electric

Weathershields to create NEMA 3R rated Transformers


It is simply the same weathershield kit number for the standard enclosure with a ``SS`` suffix added.

For example, an EE75T3HSS is in enclosure 20D. A standard 20D enclosure uses a WS364. Thus, the stainless steel weathershield kit for the EE75T3HSS is a WS364SS. All of the stainless steel weathershield kits are system recognized allowing the SquareD/Schneider Electric Distributor instant access to pricing and availability.