What is the replacement handle for a 9421FN1?

Current replacement operating mechanism will be a Class 9421 Type L operating mechanism depending on the old mounting depth:
Class 9421 LN1
Class 9421 LN3
Class 9421 LN4

NOTE: The cutomer will be forced to drill new holes in the door in order to mount the new handle because the shaft location relative to the old shaft position will be different.
A steel cover plate large enough to cover up the old handle mounting holes and provide a base for the new handle is strongly suggested. The new handle will not cover up all the old handle holes.

Detailed handle dimensional comparison between the old Type F and new Type L operating mechanism is available upon request by contacting the Customer Information Center at 1-888-SQUARED.