Technical FAQs

Ask a Question

How do you work with breaker mounting space given on the I-Line panelboard charts?

The figure is the total of mounting space for both sides of the panel, on panel interiors that have two sides. Divide it by half to know what your mounting space total is for each side. Be sure that you are choosing the right type of breakers for your panel, and that the sum of their heights is less than or equal to total breaker mounting space.


CTA-ID : 2015267
Was this helpful?
What can we do to improve the information ?