Technical FAQs

Ask a Question

How can the ATV58 be run with no motor to check the output voltages?

Confirm that the unit is at least version 4.1 IE25.  (Any version earlier than this will not be able to run this test and output would be unstable.)

Go into menu 7 and save the existing programming to a file to be recalled when the testing is done.

Go to the macro-configuration menu and set unit up for material handling (Hdg).
Go to menu 3 (drC) Enter into the Special Motor parameter (code SPC).
Set it to PSM (Small Motor)

Also, set the OPL (output phase loss) in the FLt (fault menu) to no.

Return settings to normal when done.
See the keypad programming manual for additional details.

CTA-ID : 2014919
Was this helpful?
What can we do to improve the information ?