How many auxiliary contacts can be installed on a NEMA size 0, 1, or 2 reversing contactor or starter?

Qty (2) are allowed for each 4-pole contactor; however, they must all be installed on the outer side of the contactor, as the mechanical interlock between the contactors prevents any auxiliary contacts from being installed on the inner side.