Can an isolated ground bar and neutral be installed on an 800 amp I-Line panel?

Issue:
Can an isolated ground bar and neutral be installed on an 800 amp I-Line panel?

Product Line:
I Line panelboard

Environment:
Application

Cause:
Clarification

Resolution:
The neutral assembly is insulated/isolated as normal in the Digest. An HC2SN neutral kit , for example, can be used as an aluminum isolated ground bar. If a copper neutral bar is required, use part number 40517-424-51.


Revised 4/27/04