Customer wanted to know if Square D offers a compression lug kit for EDB/EGB/EJB breakers?

Issue:
Does Schneider Electric offer compression lugs for EDB, EGB, and EJB breakers?

Product Line:
EDB, EGB, EJB type circuit breakers

Environment:
Panelboards

Cause:
Compression lugs required for use on E-frame breakers in NF panelboard

Resolution:
VC100FD is an optional aluminum compression lug for all 15-125 amp breakers.  Wire range #8–#1/0 AWG Al/Cu
CVC100FD is an optional copper compression lug for all 15-125 amp breakers. Wire range #6-#1/0 Cu