Technical FAQs

Ask a Question

Is a retaining kit required when you install a QOB3100 in an NQOD panel as a backfed main?

An NQOD panel does not need a main breaker retaining kit like those used in load centers since the QOB is a bolt-on breaker.

CTA-ID : 2013492
Was this helpful?
What can we do to improve the information ?