Can the Class 9065 Motor Logic Solid State Overload Relays be used on single-phase applications?

Product Line:
Class 9065 Solid State Overload Relays
For devices that are Series A, B, C, D, or E this overload relay should not be used on single-phase applications.

Series F devices can be used on single phase applications as long as you loop the legs, as current must be running across all three legs.

No matter the series these devices should not be used on high-leg delta, open delta, or grounded B phase (corner grounded) or rotophase applications.