In EZM Branch Devices, are the Tenant breakers on the line or load side of the meter socket?

Issue:
Design Features

Product Line:
EZM Metering

Environment:
Tenant breaker position

Cause:
Customer request

Resolution:
The Tenant breakers in the EZM branch devices are on the load side of the meter socket. This is known as Hot Sequence Metering and if the tenant breaker was on the Line side of the meter socket that would be Cold Sequence Metering. Square D does not make or offer EZM branch devices in Cold Sequence (OR with the tenant breaker on the Line Side of the meter socket).