Customer asks if the 9001BG201 start/stop push button station is for a 3ph starter?

Customer was advised that the start/stop contacts are wired into the coil circuit of the starter. It does not matter whether the starter is 3ph or 1ph. The contacts simply make and breaker the coil circuit.