How do you set the ATS48 softstarter for a Heavy (Severe) Duty Application?

Oversize the ATS48 by one size, based on the motor FLA rating.
Set the overload class to 20.
Set current limit to 350%
Set the acceleration rate to 15 seconds.
There is no switch or setting to designate ``Heavy Duty``