Technical FAQs

Ask a Question

Can we mount a 45KVA 3 phase CPT in an HVL lineup. Can it be configured with a HVL feeder switch feeding it?<br />Job also has 1350E fuses on the main switch.

Yes, this will require a 48`` wide empty section
The 1350E fuses also require a 38`` wide section.
New TAG Number 353 was created.
This TAG is for a CPT in a 48`` wide section and drawout CPT fuses.

CTA-ID : 2011545
Was this helpful?
What can we do to improve the information ?