What are the number of operations for an medium voltage switchgear?<br /><br />See resolution operations for all products.

NUMBER OF OPERATIONS

600A Switch: 5kV HVL 15kV HVL 5kV HVL/cc 15kV HVL/cc

No Load 600 600 1000 1000
Full Load 50 30 100 100


1200A Switch: 5kV HVL 15kV HVL 5kV HVL/cc1 5kV HVL/cc

No Load 250 250 1000 1000
Full Load 20 10 26 26

MiniBreak Switch 5kV 200A

No Load Operations 750
Full Load Operations 100

Visi/Vac Circuit Interrupter

No Load Operations 5000
Full Load Operations 2500

MetalClad Circuit Breaker

No Load Operations 10000
Full Load Operations 5000