Can additional contact blocks be stacked on 9001K35H2 joystick?

Clarify if additional contact blocks can be added to a 9001K35H2 joystick.
Product Line:
30mm Push Button
9001 Type K Heavy Duty Specialty Operators
Additional contact blocks are needed for application.
A maximum of 2 more contact blocks can be added. If (2) 9001KA1`s are added, there will be (2) contacts that close in each position (excluding the OFF position).