What is the maximum fuse ratings for 25kV and 38kV HVL/cc switchgear?

Issue:
What is the maximum fuse ratings for 25kV and 38kV HVL/cc switchgear?

Product Line:
HVLcc.

Environment:
Products sold in the United States.

Cause:
Application.

Resolution:
The maximum fuse ratings for 25kV and 38kV HVL/cc switchgear are:

25kV - 180A (2 - 100E fuses in parallel)
38kV - 117A (2 - 65E fuses in parallel)




CTA-ID : 2011448