How can you take Altivar ATV28 unit back to factory defaults.

Issue:   How can you take Altivar ATV28 unit back to factory defaults.
 
Product Line:   ATV28
 
Environment:  All
 
Cause:   Factory setting
 
Resolution:   This can be done by accessing menu drC (drive menu) and setting FCS (return to factory settings) to YES.
This returns the drive to factory default settings.
This will remove all settings previously made.


 