Can A.B.Chance ground studs be added to the incoming section of an HVL/cc switch lineup.

No. A.B.Chance ground studs cannot be added to the incoming section of an HVL/cc switch lineup. The clearances are less than normal in HVL/cc switchgear.

Ground studs would cause internal arcing. An option is to use a main HVL/cc switch with the ground switch option.

Caution must be taken the user must have control of the incoming source.


CTA-ID : 2011924