Technical FAQs

Ask a Question

Does the AFI breaker work with a surge strip?

Surge strips use MOV`s which will develop leakage over time, especially if they handle surges. Out of the box, there should be no problems, but older ones can have enough leakage to ground to cause the AFI to trip on GF.


CTA-ID : 2011893
Was this helpful?
What can we do to improve the information ?