Customer asks what is the difference between the QOB230 and the QOB230H

The QOB230 is rated 120/240 Vac, which means the line to ground voltage can not exceed 120 Vac. The latter is rated 240 Vac which means the line to ground voltage can be as high as 240 Vac.