Does the QOM2 Main Disconnect used in the CM200S and C2M200S Combination Service Entrance devices series rated with NQOD panelboards?

Issue:
Product design

Product Line:
Combination Service Entrance Devices and Panelboards.

Environment:
Series SCCRs

Cause:
Application 

Resolution:
No. The QOM2 does not series rate with the NQOD panelboard. For series ratings with the panelboards see the specific information for the panelboard.