How does a DC application effect the use of the trip curve for a KAL36150?

The Thermal data does not change. The magnetic data needs a multiplier applied to the trip setting. The Low setting uses 1.3X
The High setting uses 1.15 X
The multipliers will be different for other breaker frame sizes.

CTA-ID : 2009784