Is the 2510K a suitable device for use in a lockout / tagout application?

Issue: Is the 2510K a suitable device for use in a lockout / tagout application?

Product Line: 2510 type K manual switches

Environment: Products sold and used in the United States

Cause: would like to use the 2510 type K switch for LOTO application

Resolution: The 2510KG2 is a UL508 controller, not a UL98 fusible or non-fusible disconnect switch nor a UL489 circuit breaker disconnect. As such, this device is not suitable for use as a lockout device.