Technical FAQs

Ask a Question

Why can`t I select sub feed or thru feed lug options on a main lug only panel with a high AIC rating?

The UL 3 cycle rule will not allow you to feed to multiple section panels with high AIC ratings. A possible solution would be to series rate to either a remote or integral main.

Revised 3/10/04

CTA-ID : 2009716
Was this helpful?
What can we do to improve the information ?