Toyota is planning a shutdown and their question is how to ground metalclad swgr main bus and there is no access to bare bus to connect grounding clamps.

The recommended method of grounding main bus in the absents of ground studs is the usage of Manual Ground Test Device or electrical Ground Test Device [MGTD or EGTD]. An email was send to Dwaine with links to MGTD and EGTD manuals.