Technical FAQs

Ask a Question

Can a main lug I-Line panel be mounted as top or bottom feed?

Issue:
Incoming feed

Product Line:
Panelboards

Environment:
I-Line

Cause:
Mounting flexibility

Resolution:
Yes. I-Line main lug panels can be rotated in the field to accept top or bottom feed.

NOTE: Rotating the interior will affect the location of larger breakers (wide side only) on HCW / HCP, HCWM and HCWM-U / HCR-U. On a bottom feed interior, the ``wide side`` is on the left of the bus stack. On a top feed interior, the ``wide side`` is on the right side of the bus stack.


CTA-ID : 438

Was this helpful?
What can we do to improve the information ?