Can a 400A HCM panel with a vertically mounted LAP36400 main breaker be converted from bottom to top feed?

Issue:
Can a 400A HCM panel with a vertically mounted LAP36400 main breaker be converted from bottom to top feed?

Product Line:
I Line panelboard

Environment:
Installation /Application

Cause:
Clarification

Resolution:
Yes by doing the following:

1. Rotate entire panel assembly 180 degrees.

2. Replace factory installed Main breaker with a top-feed breaker. (Example: LAP36400MT)

3. In some cases, the Main breaker cover plate (part of interior deadfront) must also be rotated 180 degrees to achieve proper orientation of deadfront labels.