Are there any limitations in which branch circuit breakers can be mounted next to the QO2150, QO2175, QO2200 branch circuit breakers or QO2225SL sub-feed lug kit?

Issue:
Product limitations

Product Line:
Homeline Branch Circuit Breakers and Sub-Feed Lug kits

Environment:
Branch breaker mounting

Cause:
Application

Resolution:
Yes, due to the size of the load conductors and their exit parallel to the side wall of the load center enclosure, certain branch circuit breaker ampacities cannot be mounted next these branch breakers.

For placing breakers below the breaker when mounted on the right side or above it when mounted on the left side, you would need to make sure enough wire bending space is available for whatever wire is being used with the breaker that is wanting to be placed next to it.

For placing breakers across from it, no breaker more than 70 A can be placed across from these breakers.