Technical FAQs

Ask a Question

What procedure does SquareD/Schneider Electric use to test the sound level of a Low Voltage Dry Type Distribution Transformer?

Issue:
Sound level for Transformers

Product Line:
LV Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Cause:
Transformer noise level during operation

Resolution:

SquareD/Schneider Electric tests Low Voltage Dry Type Transformers per NEMA ST-20 Section 4.2.10 (1992). Following are some paraphrased excerpts from that standard.

- Ambient Noise must be 5 decibels below testing value (Prefered 10 decibels) Correction factor used for 5 to 10 dB below
- No acoustically refecting surface, other than the floor, with in 10 feet
- Equipment must be in accordance with ANSI S1.4, 1983
- average sound is the arithmetic mean of the sound readings (Minus correction factor)
- Five major sound producing surfaces
- ~ 1 foot from each surface @ 1/2 height (less than 8 feet tall)

For a complete print of the NEMA ST20 Standard, you must purchase the standard from NEMA as it is copyrighted material.


CTA-ID : 2000318
Was this helpful?
What can we do to improve the information ?