Technical FAQs

Ask a Question

Can the larger Homeline branch breakers, catalog numbers HOM2150BB, HOM2175BB, HOM2200BB or sub feed lug kit HOML2225 be used in any Homeline load center?


ISSUE:
Homeline large branch circuit breakers

Product Line:
Homeline Load Centers.

Environment: 
Homeline Branch Circuit Breakers

Cause:
Applicatin and Installation of large branch breakers

Resolution:
No, these branch breakers and the sub-feed lug kit can ONLY be applied in a Square D Homeline convertible mains, single phase load center, Series S01, S02, S03 and S04, RATED 150 AMPERE OR GREATER. The branch breaker ampacity cannot exceed the load center mains ampacity rating.

NOTE: DO NOT USE in other manufacturers load centers or panelboards. Please refer to the Installation Bulletin supplied with the device for further restrictions regarding mounting these devices or adjacent branch circuit breakers.


CTA-ID : 2006505
Was this helpful?
What can we do to improve the information ?