Do we offer an NW current limiting circuit breaker?

No. The NW L1 breakers do limit current at the higher current levels near or at the interrupting rating. However, they do not limit current at the mid to lower current levels which are required by UL to call them ``current limiting`` breakers. Therefore, we do not market them as current limiting breakers and have no published let-thru data for them.