What quantity and size of conductors will a GTK03 ground bar accept?

This equipment ground kit has 2 terminals and each terminal will accept (1) #14 - #4 or (2) #14 - #12 copper conductors, or (1) #12 - #4 or (2) #12 - #10 aluminum conductors. The ground bar is 1.05 inches long.