Technical FAQs

Ask a Question

Is there an adapter for connecting an old I-Line I busway to a new I-Line II busway?

Issue:
Is there an adapter for connecting an old I-Line I busway to a new I-Line II busway?

Product Line:
ILINE I Busway and ILINE II Busway

Environment:
Application using existing ILINE I Busway

Resolution:
Yes, you would add suffix 12S to I-Line II busway prefix if existing busway ends with a bolted end. You would add suffix 12B if existing busway ended with a slotted end. An example part number would be AF2516G12B.



Note
  • The adapter will take 12 in. This should be consider when replacing existing busway.

See the Busway Systems Catalog 5600CT9101 for more information
CTA-ID : 16005
Was this helpful?
What can we do to improve the information ?