What is the torque requirement and mounting screw size for a PKOGTA2 Equipment Ground Kit?

Issue:
Product Features

Product Line:
Heavy Duty Safety Switches

Environment:
Switch accessories

Cause:
Clarifying torque requirements

Resolution:
The wire binding screws should be torqued to 200 lb-in.
The mounting screw is a 12-24 x 0.640" hex/slot washer head and should be torqued to 25 - 45 lb/in. The screw is THREAD FORMING screw. Do not substitute a SELF TAPPING screw.
To purchase the mounting screw, order part number 4020506501 (1 required).
 