Does Square D offer Generator Interlock Kits for the Combination Service Entrance Devices(CSED)?

Issue:
Product availability

Product Line:
Combination Service Entrance Devices

Environment:
Generator interlock kits

Cause:
Application

Resolution:
Yes, BUT the Generator Interlock Kits are available ONLY for certain CSED catalog numbers and the below catalog numbers are the ONLY devices that can be used with a generator kit. Any other CSED catalog number would NOT allow the use of a generator kit.

The RCGK2 can be used with the following catalog numbers: "RC816F_ _ _C" or "RC816F_ _ _CH" and "RC2040M_ _ _C" or "RC2040M_ _ _CH" or "SO2040M_ _ _S". Where the '_ _ _' is the amperage of device.

The QCGK3 can be used with the following catalog numbers: "QC816F_ _ _C" or "QC816F_ _ _CH" and "QC2442M_ _ _C" or "QC2442M_ _ _CH". Where the '_ _ _' is the amperage of device.

The HOMCGK2C can be used with the following catalog numbers: "RC816F_ _ _(S / SH / SL / SS / SLS / SHS)" and "RC2040M_ _ _(S / SH / SS / SHS)" and "RC3040M_ _ _(SL / SLS)". Where the "_ _ _" is the amperage and the letters in the ( ) would be potential suffixes of the catalog number.

The QOCGK2C can be used with the following catalog numbers: "QC816F_ _ _(S / SH / SL / SS / SLS)" and "QC2442M_ _ _(S / SH / SS / SHS)" and QC3040M_ _ _SH". Where the '_ _ _' is the amperage of the device and the letters in the ( ) would be potential suffixes of the catalog number.    

NOTE: There are NO generator interlock kits for the 400amp CSED devices.