Technical FAQs

Ask a Question

Video: How does one bond the neutral to the enclosure in a QO or HOMELINE load center?

Issue:
Product design feature

Product Line:
QO and Homeline load centers

Environment:
Box Bonding

Cause:
Application

Resolution:
Refer to the Wiring Diagram of each load center, located on the interior sidewall of the enclosure. The Wiring Diagram will state "Box bonding when required" and indicate the location on the neutral assembly to install the green bonding screw. The green bonding screw, which is a self-tapping screw, will be supplied with load centers that are marked as suitable for use as service equipment.

QO Load Center Neutral Bonding Screw:


Homeline Load Center Neutral Bonding Screw:
Was this helpful?
What can we do to improve the information ?