How do you know if you have the correct torque for the joint bolt of a I-line I busway or the joint-pak for I-line II busway?

The torque is correct when the outer head, of the double-headed joint bolt, twists off. If the head has been previously twisted off, torque the bolt to 70 lb-ft, +/- 10 lb-ft.