Do you need continuous or momentary power to latch and un-latch the 8501KL12 relay since it does not have coil clearing contacts?

Issue:
Do you need continuous or momentary power to latch and un-latch the 8501KL12 relay since it does not have coil clearing contacts?
Product Line:
General Purpose Relays 
Environment:
Square D Plug-In Relay
Cause:
Determine if continuous power is needed for this relay.    
Resolution:
The relay is designed to latch and unlatch with either continuous or momentary power.